RFWS-300AB
FOR UP TO 600HP (20,700 PPH) RENTAL FEEEDWATER SYSTEM

About the RFWS-300AB
Rental Feedwater System

All components are shipped loose for field installation. This package includes the following:

750-Gallon Feedwater Tank

  • Level control
  • Sight glass assembly
  • Duplex pumps (one per boiler)
  • Chemical injection quills with metering pumps

Duplex Water Softening System

  • (2) Tank system — one in operation, one in standby for continuous soft water
  • 300K grain capacity based on 10 grain setting
  • Brine tank

Duplex Blowdown System

  • Capacity for (2) 300HP boilers
  • Aftercooler
RFWS-300AB Complete Feedwater System

Key Features of The RFWS-300AB
Rental Feedwater System

The RFWS-300AB feedwater system is highly efficient and essential to boiler operation. The two feedwater pumps provide redundancy to ensure continuous performance of the feedwater system, and the included blowdown system will help to prevent corrosion buildup, which will help to ensure that the boiler system is reliable and long-lasting.

This rental package contains everything you need for efficient operation of the feedwater system. Upon request, our factory-trained and OSHA-certified service technicians will install the system and assist you with start-up so that everything can get running as quickly and smoothly as possible.

Rental Feedwater Package

  • Helps maintain peak efficiency and prolong the life of boilers.
  • Automatically supplements condensate with makeup water to replace system losses.
  • Cold water is heated by mixing with hot condensate and pumped to the boiler on demand.

RFWS-300AB RENTAL FEEDWATER SYSTEM


Request a Quote

RFWS-300AB
Rental Feedwater System SPECIFICATIONS AND DATA

750 Gallon Feedwater Tank

  • Level control
  • Sight glass assy.
  • Duplex pumps (1 per boiler)
  • Chemical injection quills (2) with metering pumps (2)

Connection Sizes

  • Soft water inlet: 1” NPT
  • Condensate return: 2-1/2” NPT
  • Vent: 4” NPT
  • Pump outlet x2: 1-1/4” NPT

Electrical Requirements: 460v 60hz 3-phase, 100AMP

Dimensions: 114” L x 52” W x 102” H

Weight: 2400 lbs.

Freight, installation (hook-up), start-up and operator training are available through Smith Hughes upon request.

For the feedwater tank, the shipping weight is 2,400 pounds, and connection sizes include:

  • Soft water inlet: 1” NPT
  • Condensate return: 2-1/2” NPT
  • Vent: 4” NPT
  • Pump outlet x2: 1-1/4” NPT

Electrical requirements are 460v 60hz 3-phase, 25AMP.

For the duplex water softening system, the shipping weight is 1,300 pounds, and connection sizes include feedwater: 2” NPT.

Electrical requirements are 110v, 15AMP.

And for the duplex blowdown system, the shipping weight is 1,920 pounds, and connection sizes follow:

  • Blowdown: 2” 600# Flanged
  • Aftercooler: 2” 150# Flanged
  • Drain: 8” 150# Flanged
  • Vent: 12” 600# Flanged

Freight, installation (hook-up), start-up and operator training are available through Smith Hughes upon request.

Smith Hughes has been in business for more than 70 years. With our experience and expertise, you can trust that we will provide you with the perfect rental. Our service technicians are also OSHA- and factory-trained to install your rental as well as assist you with start-up and provide any necessary maintenance upon request.

We are based in Cincinnati, Ohio, and we provide nationwide service to residences and companies, which means we can get you your RFWS-300AB boiler feedwater system rental no matter what your location may be. We also operate 24/7/365, so you can have the equipment and services you need whenever you need them. And if you ever need an emergency rental, Smith Hughes will always be available to help.

If you have planned outages or repairs scheduled for your regular unit, bringing in a rental unit will enable you to continue operating so that you don’t have to sacrifice production.

Whatever your reason may be for renting, this unit is a great choice for a feedwater system.